Add to MyChemicals Print Friendly Page
Chemical Datasheet

PETROLEUM ETHER

3 - Flammable liquid
Chemical Identifiers | Hazards | Response Recommendations | Physical Properties | Regulatory Information | Alternate Chemical Names

Chemical Identifiers

CAS Number - Chemical Abstracts Service registry number. Unique identification number assigned to this chemical by the American Chemical Society.

UN/NA Number - The United Nations-North America number (also called UN number or DOT number). 4-digit number identifying an individual chemical or group of chemicals with similar characteristics. Required on shipping papers; often shown on placards or labels. This numbering system was developed by the U.S. Department of Transportation, and then became the UN standard system for classifying hazardous materials.

DOT Hazard Label - U.S. Department of Transportation hazard warning label for the chemical (such as flammable liquid or corrosive). This label must be displayed on shipped packages, railroad tank cars, and tank trucks according to specifications described in 49 CFR 172.

CHRIS Code - 3-letter code used by the U.S. Coast Guard to identify individual chemicals included in its CHRIS (Chemical Hazards Response Information System) manual.

NFPA 704 - Text description of the diamond-shaped placard, which contains codes indicating the level of the chemical's health, flammability, and instability hazards, along with special hazards such as water- and air-reactivity. See a guide to the NFPA diamond.

General Description - Brief description of the chemical's general appearance, behavior, and hazardousness.

List of data sources.
CAS Number UN/NA Number DOT Hazard Label CHRIS Code
  • 8002-05-9
  • Flammable Liquid
none
NFPA 704
data unavailable
General Description
Colorless liquid with a gasoline- or kerosene-like odor. A mixture of paraffins (C5 to C13). May contain a small amount of aromatic hydrocarbons. Flash point ranges from -40° F to -86° F

Hazards

Reactivity Alerts - Special alerts if the chemical is especially reactive (see list of reactivity alerts).

Air & Water Reactions - Special alerts if the chemical reacts with air, water, or moisture.

Fire Hazard - Description of the chemical's fire hazards (such as flammability, explosion risk, or byproducts that may evolve if the chemical is burned).

Health Hazard - Description of the chemical's health hazards (such as toxicity, flammability, or corrosivity).

Reactivity Profile - Description of the chemical's potential reactivity with other chemicals, air, and water. Also includes any other intrinsic reactive hazards (such as polymerizable or peroxidizable).

Reactive Groups - List of reactive groups that the chemical is assigned to, based on its known chemistry. Reactive groups are categories of chemicals that react in similar ways because their chemical structures are similar. Reactive groups are used to predict reactivity when you add a chemical to MyChemicals. Read more about reactive groups.

Potentially Incompatible Absorbents - Absorbents are products that can be used to soak up liquids from spills. However, some absorbents can react with particular chemicals (that is, they are incompatible), so caution should be used in selecting the correct absorbent for your situation. This section provides a list of potentially incompatible absorbents that have been known to react with liquids assigned to one or more of the reactive groups listed on this datasheet. Read more about absorbents, including situations to watch out for.

List of data sources.
Reactivity Alerts
Air & Water Reactions
Highly flammable. Insoluble in water.
Fire Hazard
Excerpt from GUIDE 128 [Flammable Liquids (Non-Polar / Water-Immiscible)]:

HIGHLY FLAMMABLE: Will be easily ignited by heat, sparks or flames. Vapors may form explosive mixtures with air. Vapors may travel to source of ignition and flash back. Most vapors are heavier than air. They will spread along ground and collect in low or confined areas (sewers, basements, tanks). Vapor explosion hazard indoors, outdoors or in sewers. Those substances designated with a (P) may polymerize explosively when heated or involved in a fire. Runoff to sewer may create fire or explosion hazard. Containers may explode when heated. Many liquids are lighter than water. Substance may be transported hot. For UN3166, if Lithium ion batteries are involved, also consult GUIDE 147. If molten aluminum is involved, refer to GUIDE 169. (ERG, 2012)
Health Hazard
Vapor irritates respiratory tract, causes coughing and mild depression. Aspiration causes severe lung irritation with coughing, gagging, and rapidly developing pulmonary edema. Ingestion irritates mouth and stomach, causes nausea, vomiting, swelling of abdomen, cardiac arrhythmias. (USCG, 1999)
Reactivity Profile
Saturated aliphatic hydrocarbons, which are contained in PETROLEUM ETHER, may be incompatible with strong oxidizing agents like nitric acid. Charring of the hydrocarbon may occur followed by ignition of unreacted hydrocarbon and other nearby combustibles. In other settings, aliphatic saturated hydrocarbons are mostly unreactive. They are not affected by aqueous solutions of acids, alkalis, most oxidizing agents, and most reducing agents. When heated sufficiently or when ignited in the presence of air, oxygen or strong oxidizing agents, they burn exothermically to produce carbon dioxide and water. May be ignited by strong oxidizers.
Belongs to the Following Reactive Group(s)
Potentially Incompatible Absorbents

No information available.

Response Recommendations

Isolation and Evacuation - Isolation and evacuation distance recommendations from the Emergency Response Guidebook (ERG).

Firefighting - Response recommendations if the chemical is on fire (or near a fire).

Non-Fire Response - Response recommendations if the chemical isn't on fire (or near a fire).

Protective Clothing - Recommendations for protective gear.

Dupont Tychem® Suit Fabrics - A table of normalized breakthrough times for DuPont Tychem suit fabrics for the chemical, if available.

First Aid - Recommended first aid treatment for people exposed to the chemical.

List of data sources.
Isolation and Evacuation
Excerpt from GUIDE 128 [Flammable Liquids (Non-Polar / Water-Immiscible)]:

As an immediate precautionary measure, isolate spill or leak area for at least 50 meters (150 feet) in all directions.

LARGE SPILL: Consider initial downwind evacuation for at least 300 meters (1000 feet).

FIRE: If tank, rail car or tank truck is involved in a fire, ISOLATE for 800 meters (1/2 mile) in all directions; also, consider initial evacuation for 800 meters (1/2 mile) in all directions. (ERG, 2012)
Firefighting
Excerpt from GUIDE 128 [Flammable Liquids (Non-Polar / Water-Immiscible)]:

CAUTION: All these products have a very low flash point: Use of water spray when fighting fire may be inefficient. CAUTION: For mixtures containing alcohol or polar solvent, alcohol-resistant foam may be more effective.

SMALL FIRE: Dry chemical, CO2, water spray or regular foam.

LARGE FIRE: Water spray, fog or regular foam. Do not use straight streams. Move containers from fire area if you can do it without risk.

FIRE INVOLVING TANKS OR CAR/TRAILER LOADS: Fight fire from maximum distance or use unmanned hose holders or monitor nozzles. Cool containers with flooding quantities of water until well after fire is out. Withdraw immediately in case of rising sound from venting safety devices or discoloration of tank. ALWAYS stay away from tanks engulfed in fire. For massive fire, use unmanned hose holders or monitor nozzles; if this is impossible, withdraw from area and let fire burn. (ERG, 2012)
Non-Fire Response
Excerpt from GUIDE 128 [Flammable Liquids (Non-Polar / Water-Immiscible)]:

ELIMINATE all ignition sources (no smoking, flares, sparks or flames in immediate area). All equipment used when handling the product must be grounded. Do not touch or walk through spilled material. Stop leak if you can do it without risk. Prevent entry into waterways, sewers, basements or confined areas. A vapor suppressing foam may be used to reduce vapors. Absorb or cover with dry earth, sand or other non-combustible material and transfer to containers. Use clean non-sparking tools to collect absorbed material.

LARGE SPILL: Dike far ahead of liquid spill for later disposal. Water spray may reduce vapor; but may not prevent ignition in closed spaces. (ERG, 2012)
Protective Clothing
Skin: Wear appropriate personal protective clothing to prevent skin contact.

Eyes: Wear appropriate eye protection to prevent eye contact.

Wash skin: The worker should immediately wash the skin when it becomes contaminated.

Remove: Work clothing that becomes wet should be immediately removed due to its flammability hazard(i.e. for liquids with flash point < 100°F)

Change: No recommendation is made specifying the need for the worker to change clothing after the work shift. (NIOSH, 2003)
DuPont Tychem® Suit Fabrics
Tychem® Fabric Legend
QC = Tychem QC
SL = Tychem SL
TF = Tychem F
TP = Tychem ThermoPro
C3 = Tychem CPF 3
BR = Tychem BR
LV = Tychem LV
RC = Tychem Responder® CSM
TK = Tychem TK
RF = Tychem Reflector®
Testing Details
Permeation data obtained per ASTM F739. Normalized breakthrough times (the time at which the permeation rate is equal to 0.1 µg/cm2/min) reported in minutes. All liquid chemicals have been tested between approximately 20°C and 27°C unless otherwise stated. All chemicals have been tested at a concentration of greater than 95% unless otherwise stated. Chemical warfare agents (Lewisite, Sarin, Soman, Sulfur Mustard, Tabun and VX Nerve Agent) have been tested at 22°C and 50% relative humidity per military standard MIL-STD-282.
Normalized Breakthrough Times (in Minutes)
Chemical CAS Number State QC SL TF TP C3 BR LV RC TK RF
Crude oil 8002-05-9 Liquid imm. >480 >480 >480 >480 >480 >480
> indicates greater than.
"imm." indicates immediate; having a normalized breakthrough time of 10 minutes or less.
A blank cell indicates the fabric has not been tested. The fabric may or may not offer barrier.

Special Warnings from DuPont

  1. Serged and bound seams are degraded by some hazardous liquid chemicals, such as strong acids, and should not be worn when these chemicals are present.
  2. CAUTION: This information is based upon technical data that DuPont believes to be reliable. It is subject to revision as additional knowledge and experience are gained. DuPont makes no guarantee of results and assumes no obligation or liability...
    ... in connection with this information. It is the user's responsibility to determine the level of toxicity and the proper personal protective equipment needed. The information set forth herein reflects laboratory performance of fabrics, not complete garments, under controlled conditions. It is intended for informational use by persons having technical skill for evaluation under their specific end-use conditions, at their own discretion and risk. Anyone intending to use this information should first verify that the garment selected is suitable for the intended use. In many cases, seams and closures have shorter breakthrough times and higher permeation rates than the fabric. Please contact DuPont for specific data. If fabric becomes torn, abraded or punctured, or if seams or closures fail, or if attached gloves, visors, etc. are damaged, end user should discontinue use of garment to avoid potential exposure to chemical. Since conditions of use are outside our control, we make no warranties, express or implied, including, without limitation, no warranties of merchantability or fitness for a particular use and assume no liability in connection with any use of this information. This information is not intended as a license to operate under or a recommendation to infringe any patent or technical information of DuPont or others covering any material or its use.

(DuPont, 2013)

First Aid
Eye: If this chemical contacts the eyes, immediately wash the eyes with large amounts of water, occasionally lifting the lower and upper lids. Get medical attention immediately. Contact lenses should not be worn when working with this chemical.

Skin: If this chemical contacts the skin, promptly wash the contaminated skin with soap and water. If this chemical penetrates the clothing promptly remove the clothing and wash the skin with soap and water. Get medical attention promptly.

Breathing: If a person breathes large amounts of this chemical, move the exposed person to fresh air at once. If breathing has stopped, perform mouth-to-mouth resuscitation. Keep the affected person warm and at rest. Get medical attention as soon as possible.

Swallow: If this chemical has been swallowed, get medical attention immediately. (NIOSH, 1997)

Physical Properties

This section contains physical properties, flammability limits, and toxic thresholds for this chemical (see definitions of each property). More property data is available for common chemicals.

See also the Levels of Concern guide for information on AEGLs, ERPGs, PACs, and IDLH values.

List of data sources.
Chemical Formula: data unavailable
Flash Point: -86 to -40 ° F (NIOSH, 2003)
Lower Explosive Limit (LEL): 1.1 % (NIOSH, 2003)
Upper Explosive Limit (UEL): 5.9 % (NIOSH, 2003)
Autoignition Temperature: data unavailable
Melting Point: -99 ° F (NIOSH, 2003)
Vapor Pressure: 40 mm Hg (approx) (NIOSH, 2003)
Vapor Density (Relative to Air): data unavailable
Specific Gravity: 0.75 at 68.0 ° F (USCG, 1999)
Boiling Point: 86 to 460 ° F at 760.0 mm Hg (NIOSH, 2003)
Molecular Weight: 99 (NIOSH, 2003)
Water Solubility: Insoluble (NIOSH, 2003)
IDLH: 1100 ppm (NIOSH, 2003)

AEGLs (Acute Exposure Guideline Levels)

No AEGL information available.

ERPGs (Emergency Response Planning Guidelines)

No ERPG information available.

PACs (Protective Action Criteria)

Chemical PAC-1 PAC-2 PAC-3
Petroleum distillates; (Petroleum crude oil) (8002-05-9) 87.5 ppm 450 ppm 10000 ppm
(SCAPA, 2012)

Regulatory Information

This section contains regulatory information from the Title III Consolidated List of Lists (see details about each regulatory field).

List of data sources.
No regulatory information available.

Alternate Chemical Names

This section provides a listing of alternate names for this chemical, including trade names and synonyms.